hipecs CIO161 CANopen PT100/PT1000 with 2-wire technology
The hipecs-CIO161 device provides a CANopen based temperature measurement with up to 8 temperature values of PT100 or PT1000 sensors in 2-wire technology.
The readings are digitally filtered to stabilize them. The time for measuring is 20 ms. With this supply based distortions are reduced. PT100 and PT1000 sensors can be combined randomly.
CANopen is available according to DS301 and DS401.
All usual baud rates up to 1 Mbit/s supported. The device supports automatic start, with a cyclic transmission of the readings every 250 ms.
system
- operating voltage 11 .. 32V DC (typ. 24V DC)
- cable cross section 0.08 .. 1,5 qmm (AWG28 .. AWG14)
- temperature range 0 .. 55°C / -40 .. 70°C
- plastic housing for DIN rail mounting
- dimensions (LxBxH) 54 x 125 x 62 mm (with connector)
measurement channels
- 8 inputs PT100/PT1000
- 2 wire mesurement
- measurement range -100°C .. +500°C
CANopen
- 1 CAN-Bus according to ISO11898
- CAN-Baudraten adjustable up to 1 Mbit
- node number adjustable from 1 .. 127
- CANopen draft standard DS301 V4.0 / DS401 V2.1
- CANopen diagnosis LEDs
- 4 receive / 4 transmit PDOs
- 1 SDO server
- PDO event timer
- PDO inhibit timer
- PDO transmit modes: event triggered, synchronous, asynchronous, cyclic, anticyclic, remote frame
- variable PDO identifier
- dynamic PDO mapping
- emergencys
- nodeguarding/lifeguarding/heartbeat
- EDS file
ordering information
article no. | article | housing | temperature | galvanic isolation |
EZ00000.2961.00 | hipecs-CIO160-i | plastic | 0..+55 | yes |
EZ00000.3161.00 | hipecs-CIO160-ie | plastic | -40..+70 | yes |